RayCONTROL
RayCONTROL 30 is the control unit for the FCC Planterm temperature control system.
RayCONTROL 30 supports up to 30 individual zones.
Communication
RayNET is an interface module that provides a standard Modbus/RTU interface over RS485 for RayCONTROL 30. The default connection parameters are:
Modbus address: 1
RS-485 parameters:
Baud rate | 9600 |
Data bits | 8 |
Stop bit | 1 |
Parity | none |
Flow control | none |
Refer to the RayNET and RayCONTROL 30 technical documentation for installation, wiring and power supply requirements.
HSYCO connects to the Modbus bus through any standard Modbus/TCP gateway.
HSYCO Configuration
Add a RAYCONTROL I/O Server in the I/O Servers section of the Settings and set its parameters:
Communication
- Comm ID: select a MODBUSTCP I/O server if using a Modbus gateway, or the serial port id when using a direct RS-485 port with HSYCO acting as Modbus RTU master.
High Availability
- Shutdown when inactive: defaults to true.
Options
ID | Default | Values | Description |
---|---|---|---|
gui | true | true | enable support for the UI object, UISET actions and USER commands |
false | disable UI support | ||
startupevents | false | true | generate IO events also during the driver’s start-up phase |
false | start generating events only after HSYCO is aligned with the current status of the system | ||
pollinterval | 30 | 1 ... 45 | the data acquisition interval, in seconds |
address | 1 | > 0 | the Modbus address of the RayCONTROL device |
readinterval | 25 | 0 ... 1000 | minimum interval between consecutive Modbus commands |
systems | 1 | 1 ... 2 | set to 1 if using only system 1; set to 2 is system 2 is used |
zones | 15 | 1 ... 30 | set to the highest zone number used |
sensivity | 5 | >0 | measured temperatures’ changes are reported only if the difference from last reading is equal or greater than the sensivity option, in 10th of Celsius degrees |
language | en | en, fr, it | the language used for text messages. If undefined, the global language option is used. English is used if the global language is also undefined |
Datapoints
ID | Value | R/W | Description |
---|---|---|---|
connection | online | R | connection established |
offline | R | HSYCO can't connect to the panel | |
s<n>.status | off | R | system <n> is off |
W | turn off system <n> | ||
on | R | system <n> is on | |
W | turn on system <n> | ||
maint | R | system <n> is in maintenance mode | |
s<n>.mode | winter | R | system <n> is in winter mode |
W | set system <n> to winter mode | ||
summer | R | system <n> is in winter mode | |
W | set system <n> to summer mode | ||
towinter | R | system <n> is in summer mode, transitioning to winter mode | |
tosummer | R | system <n> is in winter mode, transitioning to summer mode | |
s<n>.setpoint.winter.max | 160 .. 300 | R | system <n> current maximum winter temperature set-point |
W | set system <n> maximum winter temperature set-point | ||
s<n>.setpoint.winter.min | 150 .. 290 | R | system <n> current minimum winter temperature set-point |
W | set system <n> minimum winter temperature set-point | ||
s<n>.setpoint.summer.max | 160 .. 300 | R | system <n> current maximum summer temperature set-point |
W | set system <n> maximum summer temperature set-point | ||
s<n>.setpoint.summer.min | 150 .. 290 | R | system <n> current minimum summer temperature set-point |
W | set system <n> minimum summer temperature set-point | ||
s<n>.temp.out | -400 ... +800 | R | outdoor temperature, in 10th of Celsius degrees (e.g. 210 corresponds to 21.0 °C) |
s<n>.temp.inlet | -400 ... +800 | R | inlet temperature, in 10th of Celsius degrees (e.g. 210 corresponds to 21.0 °C) |
z<n>.mode | off | R | zone <n> is off |
W | turn off zone <n> | ||
maint | R | zone <n> is in maintenance mode | |
eco | R | zone <n> is in energy saving mode | |
W | set zone <n> to energy saving mode | ||
pgm | R | zone <n> is in program mode | |
W | set zone <n> to program mode | ||
man | R | zone <n> is in manual mode | |
W | set zone <n> to manual mode | ||
on | W | set zone <n> to the mode set before last off (ECO, PGM or MAN). If HSYCO starts with the zone already off, the on command sets the mode to ECO | |
z<n>.lock | 0 | R | zone <n> is not locked |
W | unlock zone <n> | ||
1 | R | zone <n> is locked | |
W | lock zone <n> | ||
z<n>.temp | -400 ... 800 | R | measured temperature, in 10th of Celsius degrees (e.g. 210 corresponds to 21.0 °C) |
z<n>.humidity | 1... 100 | R | measured relative umidity, from 0 to 100 |
z<n>.setpoint.temp | 150 ... 300 | R | zone <n> set-point temperature, in 10th of Celsius degrees (e.g. 210 corresponds to 21.0 °C) |
W | zone <n> set-point temperature, in 10th of Celsius degrees (e.g. 210 corresponds to 21.0 °C) | ||
up | W | increase zone temperature set-point by 0.5 °C | |
down | W | decrease zone temperature set-point by 0.5 °C | |
alarm.<c> | 0 | R | alarm code C (1-72) inactive |
1 | R | alarm code C (1-72) active | |
alarm | 0 | R | no active alarms |
1 | R | the system is reporting at least one active alarm |
User Interface
UISET Actions
ID | Attribute | Set to |
---|---|---|
s<n>.status | value | system <n> (1 or 2) status |
ON: system is on | ||
OFF: system is off | ||
MAINT: maintenance mode | ||
s<n>.mode | value | system <n> (1 or 2) mode: |
SUMMER: summer mode (cooling) | ||
WINTER: winter mode (heating) | ||
SUMMER*: summer, transitioning to winter mode | ||
WINTER*: winter, transitioning to summer mode | ||
s<n>.temp.out | value | the outdoor measured temperature for system <n> (1 or 2), in Celsius degrees with one decimal digit, followed by ' °C' |
s<n>.temp.inlet | value | the inlet measured temperature for system <n> (1 or 2), in Celsius degrees with one decimal digit, followed by ' °C' |
z<n>.mode | value | zone <n> operating mode: |
OFF: zone is off | ||
ECO: energy saving mode | ||
PGM: program mode; the zone follows a set-point during a defined time period | ||
MAN: manual mode; constantly follows the temperature set-point | ||
MAINT: zone in maintenance mode | ||
z<n>.lock | value | zone lock mode: |
LOCKED: zone is locked | ||
'': zone is not locked | ||
z<n>.temp | value | the current temperature in Celsius degrees with one decimal digit, followed by ' °C' |
z<n>.humidity | value | the current relative humidity, from 0 to 100, followed by ' %' |
z<n>.setpoint.temp | value | the zone temperature set-point in Celsius degrees with one decimal digit, followed by ' °C' |
alarm.<n> | value | text line <n> (1-30) of the alarms register, with start/end date and time and error code: |
"CODE NN: YYYY-MM-DD HH:MM:SS - YYYY-MM-DD HH:MM:SS" | ||
alarm.label | value | alarm flag. This object is normally invisible, and made visible when the rayCONTROL reports at least one active alarm |
USER Commands
Name | Param | Action |
---|---|---|
z<n> | mode | cycle through the different operation modes (off, eco, pgm, man) |
z<n> | mode.off | set zone <n> off |
z<n> | mode.eco | set zone <n> to ECO (energy saving) mode |
z<n> | mode.pgm | set zone <n> to PGM (program) mode |
z<n> | mode.man | set zone <n> to MAN (manual) mode |
z<n> | mode.on | set zone <n> to the mode set before last off (ECO, PGM or MAN). If HSYCO starts with the zone already off, the on command sets the mode to ECO |
z<n> | temp.up | increase zone temperature set-point by 0.5 °C |
z<n> | temp.down | decrease zone temperature set-point by 0.5 °C |
s<n> | power | system <n> (1 or 2) power on/off button |
s<n> | mode | system <n> (1 or 2) season button, for winter/summer mode selection |
Release Notes
3.3.0
- new data points:
s<n>.setpoint.winter.max
s<n>.setpoint.winter.min
s<n>.setpoint.summer.max
s<n>.setpoint.summer.min z<n>.lock
- new readinterval option (defaults to 20 msec.)
- improved communication errors handling
3.0.0
- full integration in HSYCO 3.0.0
RayCONTROL is a registered trademark of Permasteelisa Impianti srl, FCC Planterm Division.