HwgIO
The HW group I/O Controller 2 is a general purpose digital input-output Ethernet controller, with 8 inputs and 8 outputs.
This I/O Server also supports the legacy PortBox, ER84 and ER88 conrollers.
HSYCO Configuration
Add an HWGIO I/O Server in the I/O Servers section of the Settings and set its parameters:
Communication
- IP Address: host name or IP address of the I/O Controller
- IP Port: TCP/IP port to use, leave blank to use default port 23.
High Availability
- Shutdown when inactive: defaults to true (the I/O Controller only accepts one connection and can't be accessed by two HSYCO servers simultaneously).
Options
There are no available configuration options for the HWGIO I/O Server.
I/O Controller Configuration
TCP/IP mode needs to be configured and NVT (Network virtual terminal) enabled in order to work with the digital inputs and outputs.
Refer to the I/O Controller manual for detailed configuration information.
Datapoints
The data points associated to the input pins are named i1
to i8
.
The data points associated to the output pins are named o1
to o8
.
The I/O Server generates asynchronous events based on the status of the I/O Controller's input and output pins. The output data points can be written to control the output pins.
ID | Value | R/W | Description |
---|---|---|---|
i<n> | 0 | R | input <n> is low |
1 | R | input <n> is high | |
o<n> | 0 | R | output <n> is low |
W | set output <n> to off | ||
1 | R | output <n> is high | |
W | set output N to on |
Release Notes
3.0.1
- Fixed a bug that could block the update of the systemtopo.txt file at start-up.
2.8.3
- Support of the serial port in HWg I/O Controller.
2.8.0
- Initial support.
HWg is a registered trademark of HW group s.r.o.