Felma's Alert5 is a supervisor system that can control anti-intrusion, fire prevention, access control and TVCC systems. The communication with HSYCO is via HTTP protocol.

HSYCO Configuration

Add the ALERT5 I/O Server in the I/O Servers section of the Settings and set its parameters:

Communication

  • IP Address: host name or IP address of the supervisor
  • IP Port: TCP/IP port assigned to the supervisor

Authentication

  • User: username to access the supervisor
  • Password: password to access the supervisor

Options

IDDefaultValuesDescription
startupeventsfalsetruegenerate IO events also during the driver’s start-up phase
falsestart generating events only after HSYCO is aligned with the current status of the system
pollinterval1000n > 1000the data acquisition interval, in milliseconds
logsize300n ≥ 0the number of log lines to display in the UI object

Datapoints

The hierarchical structure is: System > Area > Device (every system can contain multiple areas and every area can contain multiple devices)

IDValueR/WDescription
connectiononlineRthe driver started correctly
offlineRthe driver didn't start correctly or loop cycle failed
global.error<num>Rerror code, 0 means no error
global.desc<text>Rerror description, OK means no error
global.api.name<text>Rcurrent API name
global.api.version<val>Rcurrent API version
sys.<sys_id>.desc<text>Rdescription of sys_id
sys.<sys_id>.type<text>Rtype of sys_id
sys.<sys_id>.status.connection–1Rundefined state
0Rsys_id not online (logical state)
1Rsys_id online (logical state)
sys.<sys_id>.status.system–1Rundefined state
0Rsys_id not online (physical state)
1Rsys_id online (physical state)
sys.<sys_id>.status.alarm–1Rundefined state
0Rsys_id not in alarm
1Rsys_id in alarm
sys.<sys_id>.status.fault–1Rundefined state
0Rsys_id ok
1Rsys_id fault
sys.<sys_id>.command.<command_id>.desc<text>Rdescription of command_id associated to sys_id
sys.<sys_id>.area.<area_id>.desc<text>Rdescription of area_id
sys.<sys_id>.area.<area_id>.code<num>Rcode of area_id
sys.<sys_id>.area.<area_id>.status.connection–1Rundefined state
0Rarea_id disarmed (logical state)
1Rarea_id armed (logical state)
sys.<sys_id>.area.<area_id>.status.area–1Rundefined state
0Rarea_id disarmed (physical state)
1Rarea_id armed (physical state)
sys.<sys_id>.area.<area_id>.status.alarm–1Rundefined state
0Rarea_id not in alarm
1Rarea_id in alarm
sys.<sys_id>.area.<area_id>.status.fault–1Rundefined state
0Rarea_id ok
1Rarea_id fault
area.<area_id>.command.<command_id>.desc<text>Rdescription of command_id associated to area_id
sys.<sys_id>.area.<area_id>.dev.<dev_id>.desc<text>Rdescription of dev_id
sys.<sys_id>.area.<area_id>.dev.<dev_id>.code<num>Rcode of dev_id
sys.<sys_id>.area.<areaId>.dev.<dev_id>.status.bypass–1Rundefined state
0Rdev_id is bypassed
1Rarea_id armed
sys.<sys_id>.area.<areaId>.dev.<dev_id>.status.open–1Rundefined state
0Rdev_id is closed (or is not active)
1Rdev_id is open (or is active)
sys.<sys_id>.area.<area_id>.dev.<dev_id>.status.alarm–1Rundefined state
0Rdev_id not in alarm
1Rdev_id in alarm
sys.<sys_id>.area.<area_id>.dev.<dev_id>.status.fault–1Rundefined state
0Rdev_id ok
1Rdev_id fault
dev.<dev_id>.command.<command_id>.desc<text>Rdescription of command_id associated to dev_id
sys.<sys_id>.command.<command_id>1Wexec command_id for sys_id
area.<area_id>.command.<command_id>1Wexec command_id for area_id
dev.<dev_id>.command.<command_id>1Wexec command_id for dev_id

User Interface

UISET Actions

IDAttributeSet ToDescription
logvaluelatest security log lines (as many as specified by the 'logsize' option)
log0valuelatest security log (it will vanish after 5 seconds)
dev.<dev_id>.status.bypassvisibletruedev_id bypassed
falsedev_id not not bypassed
dev.<dev_id>.status.openvisibletruedev_id active
falsedev_id not not active
dev.<dev_id>.status.alarmvisibletruedev_id in alarm
falsedev_id not not in alarm
sys.<system_id>.descvaluedescription of system_id
sys.<system_id>.area.<area_id>.descvaluedescription of area_id included in system_id
sys.<system_id>.area.<area_id>.dev.<dev_id>.descvaluedescription of dev_id included in area_id included in system_id
sys.<system_id>.command.<command_id>.descvaluedescription of command_id of system_id
area.<area_id>.command.<command_id>.descvaluedescription of command_id of area_id
dev.<dev_id>.command.<command_id>.descvaluedescription of command_id of dev_id

Alert5 UI Object

The user interface for the Alert5 system:

Alert 5 UI Object 1 Alert 5 UI Object 2 Alert 5 UI Object 3 Alert 5 UI Object 4

The first image shows the list of configured systems, you can reset the alarm for every single system.

The second image shows all areas associated to the selected system, you can arm/disarm every single area. You can also arm/disarm alla areas of the selected system together.

The third image shows all devices associated to the selected system and area, you can activate or bypass/unbypass the device. The four icons inside device popup represents in order: state(open/closed or active/inactive), alarm, fault, bypass.

The fourth image shows the most recent logs of Alert5 system.

The icon on top of the page will turn white when an area is in alarm.

The (alert5) object is listed in the Project Editor’s new object list only when at least one Alert5 I/O Server is defined

Log Files

If a ALERT5 I/O Server is connected to HSYCO, the security.log file will be written in the same directories as the daily log files.

This file is never overwritten or deleted from HSYCO SERVER.

2021.09.10 11:02:17.357 - alert5 - HSYCO ONLINE
2021.09.10 11:44:08.740 - alert5 - 10-09-2021 11:44:07 | Evento: Transazione valida in ingresso, Apparato: GESTIONE ACCESSI CED, Area: RETRO FELMA, Dispositivo: RETRO FELMA, Anagrafica: FRIGERIO GIANNI
2021.09.10 11:44:25.923 - alert5 - 10-09-2021 11:44:25 | Evento: Transazione valida in ingresso, Apparato: GESTIONE ACCESSI CED, Area: PORTONE SCORREVOLE, Dispositivo: PORTONE SCORREVOLE, Anagrafica: CIONI MATTEO

Other information about the ALERT5 driver are stored in the message.log daily file.

Release Notes

3.8.0

  • initial release

Alert5 is a registered trademark of Felma S.r.l.