RACKPDU

The APC by Schneider Electric Rack Power Distribution Unit (PDU) may be used as a stand-alone, network- manageable power distribution device or up to four devices can be connected together using one network connection. The Rack PDU provides real-time remote monitoring of connected loads.

The HSYCO RACKPDU driver supports the AP88XX and AP78XXB Metered models.

RackPDU Conf 1

PDU Configuration

In order to be able to control the device with HSYCO SERVER, remote access to the command line interface via SSH must be enabled.

HSYCO Configuration

Add a RACKPDU I/O Server in the I/O Servers section of the Settings and set its parameters:

Communication

  • IP Address: the IP address of the device
  • IP Port: TCP/IP port to use (defaults to 22)
  • User: the SSH user (defaults to "apc")
  • Password: the SSH password (defaults to "apc").

High Availability

  • Shutdown when inactive: defaults to false.

Options

IDDefaultValuesDescription
startupeventsfalsetruegenerate IO events also during the driver’s start-up phase
falsestart generating events only after HSYCO is aligned with the current status of the system

Datapoints

All measured values returned as datapoints use the units as set in the PDU. The unit is not returned in the datapoint value.

IDValueR/WDescription
connectiononlineRconnection established
offlineRnot connected to the PDU
bklowload.<N><value>Rbank N low-load threshold current in amps
bknearover.<N><value>Rbank N near-overload threshold current in amps
bkoverload.<N><value>Rbank N overload threshold current in amps
devlowload<value>Rlow-load threshold in kilowatts for the device
devnearover<value>Rnear-overload threshold in kilowatts for the device
devoverload<value>Roverload threshold in kilowatts for the device
humreading<value>Rhumidity value from the sensor (%RH)
phlowload.<N><value>Rphase N low-load threshold (amps)
phnearover.<N><value>Rphase N near-overload threshold (amps)
phoverload.<N><value>Rphase N overload threshold (amps)
tempReading<value>Rtemperature value in Celsius
bkpeakcurr.<N><value>Rbank N peak current measurement in amps
bkreading.<N><value>Rbank N current reading (measurement) in amps
devpeakload<value>Rpeak power measurement in kilowatts from the device
devreading.power<value>Rtotal power in kilowatts for the device
devreading.energy<value>Rtotal energy in kilowatt-hours for the device
devreading.appower<value>Rtotal apparent power in kilovolt amperes for the device
devreading.pf<value>Rtotal power factor for the device
phpeakcurr.<N><value>Rpeak current measurement from phase N (amps)
phreading.current.<N><value>Rmeasured current for phase N (amps)
phreading.voltage.<N><value>Rmeasured voltage for phase N (volts)
phreading.power.<N><value>Rmeasured power for phase N (watts)
phreading.appower.<N><value>Rmeasured apparent power for phase N(va)
phreading.pf.<N><value>Rmeasured power factor for phase N
lcdonWturn the LCD on
offWturn the LCD off
lcdblink<1-10>Wblink the LCD for 1 to 10 minutes

Release Notes

3.6.0

  • initial version release