The APC by Schneider Electric Rack Power Distribution Unit (PDU) may be used as a stand-alone, network- manageable power distribution device or up to four devices can be connected together using one network connection. The Rack PDU provides real-time remote monitoring of connected loads.

The HSYCO RACKPDU driver supports the AP88XX and AP78XXB Metered models.

RackPDU Conf 1

PDU Configuration​

In order to be able to control the device with HSYCO SERVER, remote access to the command line interface via SSH must be enabled.

HSYCO Configuration​

Add a RACKPDU I/O Server in the I/O Servers section of the Settings and set its parameters:

Communication​

  • IP Address: the IP address of the device
  • IP Port: TCP/IP port to use (defaults to 22)
  • User: the SSH user (defaults to "apc")
  • Password: the SSH password (defaults to "apc").

High Availability​

  • Shutdown when inactive: defaults to false.

Options​

IDDefaultValuesDescription
startupeventsfalsetruegenerate IO events also during the driver’s start-up phase
falsestart generating events only after HSYCO is aligned with the current status of the system

Datapoints​

All measured values returned as datapoints use the units as set in the PDU. The unit is not returned in the datapoint value.

IDValueR/WDescription
connectiononlineRconnection established
offlineRnot connected to the PDU
bklowload.<N><value>Rbank N low-load threshold current in amps
bknearover.<N><value>Rbank N near-overload threshold current in amps
bkoverload.<N><value>Rbank N overload threshold current in amps
devlowload<value>Rlow-load threshold in kilowatts for the device
devnearover<value>Rnear-overload threshold in kilowatts for the device
devoverload<value>Roverload threshold in kilowatts for the device
humreading<value>Rhumidity value from the sensor (%RH)
phlowload.<N><value>Rphase N low-load threshold (amps)
phnearover.<N><value>Rphase N near-overload threshold (amps)
phoverload.<N><value>Rphase N overload threshold (amps)
tempReading<value>Rtemperature value in Celsius
bkpeakcurr.<N><value>Rbank N peak current measurement in amps
bkreading.<N><value>Rbank N current reading (measurement) in amps
devpeakload<value>Rpeak power measurement in kilowatts from the device
devreading.power<value>Rtotal power in kilowatts for the device
devreading.energy<value>Rtotal energy in kilowatt-hours for the device
devreading.appower<value>Rtotal apparent power in kilovolt amperes for the device
devreading.pf<value>Rtotal power factor for the device
phpeakcurr.<N><value>Rpeak current measurement from phase N (amps)
phreading.current.<N><value>Rmeasured current for phase N (amps)
phreading.voltage.<N><value>Rmeasured voltage for phase N (volts)
phreading.power.<N><value>Rmeasured power for phase N (watts)
phreading.appower.<N><value>Rmeasured apparent power for phase N(va)
phreading.pf.<N><value>Rmeasured power factor for phase N
lcdonWturn the LCD on
offWturn the LCD off
lcdblink<1-10>Wblink the LCD for 1 to 10 minutes

Release Notes​

3.6.0​

  • initial version release